9SX6KiRT 

Eaton 9SX 6000i RT3U UPS
 
General
Topology On-line double conversion with PFC (Power Factor Correction) system
Configuration Rack/Tower
Part Number 9SX6KiRT 
Rating (VA/Watts) 6000/5400
Dimensions (H x W x D, mm) 130 (3U) x 440 x 685
Weight (kg) 48
Warranty 2 years warranty
Rail Kit Included Yes
 
Electrical Input
Connection
Hardwired - see manual for terminal block layout
Hardwired - example layout only
Input Voltage Range 176-276V without derating (up to 100–276V with derating)
Nominal Voltage 200/208/220/230/240V
Frequency 50/60 Hz autoselection
Frequency Range 40-70 Hz
Short Circuit Current 90 A
THDI <5%
 
Electrical Output
Voltages 200/208/220/230/240V +/– 1%
Voltage THD < 2%
Output Receptacles
Hardwired - see manual for terminal block layout
Hardwired - example layout only
(8) IEC-320-C13
IEC C13
(2) IEC-320-C19
IEC C19
Overload Capacity 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms
Efficiency (Normal Mode) Up to 94% in Online mode, 98% in Hi-Efficiency mode
Output Frequency 50/60 Hz autoselect, frequency converter as standard
Load Crest Factor 3:1
 
Battery
Runtime
(Minutes)
Load (Watts)
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc. Actual runtime may vary from +/- 15% around these typical values

Show:

Hover over graph for detailed runtime values
Battery Management ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units.
Extended Battery Capability EBM with Rack Kit
 
Communications
User Interface Multilingual graphical LCD display
Communication Ports 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off
Communication Slot 1 slot for Network-MS card, ModBus-MS or Relay-MS cards.
 
Environmental & Standards
Audible Noise <45dB
Operating Temperature 0 to 40°C continuous
Safety markings IEC/EN 62040-1, UL 1778, CSA 22.2
EMC Markings IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance), C-Tick
Approvals CE, CB report (TUV), UL
   

In the interests of continuous product improvement all specifications are subject to change without notice.