Eaton 9155 UPS Technical Specs

 Stand-alone UPS with 1-phase input / 1-phase output
 Stand-alone UPS with 3-phase input / 1-phase output
 External battery cabinets
UPS output power rating (0,9 p.f.)
kVA 8 10 12 15 20 30
kW 7.2 9 10.8 13.5 18 27
General
Efficiency in double conversion mode (full load) 92% 93%
Efficiency in double conversion mode (half load) 90% 91%
Efficiency in high efficiency mode up to 98% -
Distributed paralleling with Hot Sync technology 4
Field upgradeable yes
Inverter/rectifier topology transformer-free IGBT with PWM
Audible noise < 50 dB
Altitude (max) 1000 m without derating (max 2000 m)
Input
Input wiring 1 ph or 3 ph + N + PE 3 ph + N + PE
Nominal voltage rating (configurable) 220/380, 230/400, 240/415 V 50/60 Hz
Input voltage range Low -20% at 100% load/-50% at 50% load without battery discharge; High +10%/max +20%
Input frequency range 45-65 Hz
Input power factor 0,99
Input ITHD less than 4,5%
Soft start capability Yes
Internal backfeed protection Yes
Output
Output wiring 1 ph + N + PE
Nominal voltage rating (configurable) 220/380, 230/400, 240/415 V 50/60 Hz
Output UTHD <3% (100% linear load); <5% (reference non linear load)
Output power factor 0,9 (e.g. 9 kW at 10 kVA) 0,9 (e.g. 27 kW at 30 kVA)
Permitted load power factor 0,7 lagging - 0,8 leading
Overload on inverter 10 min 100-110%; 1 min 110-125%; 5 sec 125-150%; 300 ms >150%
Overload when bypass available 60 min 100-110%, 10 min 110-125%; 1 min >125- 150%
Battery
Type Maintenance-free VRLA batteries, NiCd
Charging method ABM technology or Float
Temperature compensation Optional
Battery nominal voltage (lead-acid) 384 V (32x12 V, 192 cells) 432 V (36x12 V, 216 cells)
Charging current / Model Default 3 A
*Max 30 A
Default 3 A
*Max 60 A
*May be limited by maximum UPS input current rating
Accessories
  Isolation transformer, long-life batteries, external battery cabinets, UPS Center (input, bypass, distribution), X-Slot connectivity (Web/SNMP, ModBus/ Jbus, Relay, Hot Sync, ViewUPS-X remote display), Hot Sync parallel tie cabinet, integrated manual bypass, external maintenance bypass switch Isolation transformer, long-life batteries, external battery cabinets, X-Slot connectivity (Web/SNMP, ModBus/ Jbus, Relay, Hot Sync, ViewUPS-X remote display), Hot Sync parallel tie cabinet, integrated manual bypass, external maintenance bypass switch
Communications
X-Slot 2 communication bays
Serial ports 1 available
Relay inputs/outputs 2/1 programmable
Compliance with standards
Safety (CB certified) IEC 62040-1, IEC 60950-1
EMC IEC 62040-2
Performance IEC 62040-3

In the interests of continuous product improvement all specifications are subject to change without notice.

Stand-alone UPS with 1-phase input / 1-phase output
Part number Description Rating Back-up (p.f. 0.7) Dimensions (HxWxD) Weight
1022532 9155-8-S-10-32x7Ah 8 kVA / 7.2 kW 10 min 817x305x702 mm 155 kg
1022533 9155-8-S-15-32x9Ah 8 kVA / 7.2 kW 15 min 817x305x702 mm 160 kg
1022534 9155-8-S-28-64x7Ah 8 kVA / 7.2 kW 28 min 1214x305x702 mm 250 kg
1022535 9155-8-S-33-64x9Ah 8 kVA / 7.2 kW 33 min 1214x305x702 mm 275 kg
1022536 9155-10-S-10-32x9Ah 10 kVA / 9 kW 10 min 817x305x702 mm 160 kg
1022537 9155-10-S-20-64x7Ah 10 kVA / 9 kW 20 min 1214x305x702 mm 250 kg
1022538 9155-10-S-25-64x9Ah 10 kVA / 9 kW 25 min 1214x305x702 mm 275 kg
Stand-alone UPS with 3-phase input / 1-phase output
1022480 9155-8-N-10-32x7Ah 8 kVA / 7.2 kW 10 min 817x305x702 mm 155 kg
1022481 9155-8-N-15-32x9Ah 8 kVA / 7.2 kW 15 min 817x305x702 mm 160 kg
1022482 9155-8-N-28-64x7Ah 8 kVA / 7.2 kW 28 min 1214x305x702 mm 250 kg
1022483 9155-8-N-33-64x9Ah 8 kVA / 7.2 kW 33 min 1214x305x702 mm 275 kg
1022484 9155-10-N-10-32x9Ah 10 kVA / 9 kW 10 min 817x305x702 mm 160 kg
1022485 9155-10-N-20-64x7Ah 10 kVA / 9 kW 20 min 1214x305x702 mm 250 kg
1022486 9155-10-N-25-64x9Ah 10 kVA / 9 kW 25 min 1214x305x702 mm 275 kg
1022487 9155-12-N-8-32x9Ah 12 kVA / 10.8 kW 8 min 817x305x702 mm 160 kg
1022488 9155-12-N-15-64x7Ah 12 kVA / 10.8 kW 15 min 1214x305x702 mm 250 kg
1022489 9155-12-N-20-64x9Ah 12 kVA / 10.8 kW 20 min 1214x305x702 mm 275 kg
1022490 9155-15-N-5-32x9Ah 15 kVA / 13.5 kW 5 min 817x305x702 mm 160 kg
1022491 9155-15-N-10-64x7Ah 15 kVA / 13.5 kW 10 min 1214x305x702 mm 250 kg
1022492 9155-15-N-15-64x9Ah 15 kVA / 13.5 kW 15 min 1214x305x702 mm 275 kg
1026598 9155-20-N-5-1x9Ah-MBS 20 kVA / 18 kW 5 min 1684x494x762 mm 300 kg
1026599 9155-20-N-13-2x9Ah-MBS 20 kVA / 18 kW 13 min 1684x494x762 mm 400 kg
1026600 9155-20-N-22-3x9Ah-MBS 20 kVA / 18 kW 22 min 1684x494x762 mm 500 kg
1026601 9155-20-N-31-4x9Ah-MBS 20 kVA / 18 kW 31 min 1684x494x762 mm 600 kg
1026602 9155-30-N-7-2x9Ah-MBS 30 kVA / 27 kW 7 min 1684x494x762 mm 400 kg
1026603 9155-30-N-13-3x9Ah-MBS 30 kVA / 27 kW 12 min 1684x494x762 mm 500 kg
1026604 9155-30-N-20-4x9Ah-MBS 30 kVA / 27 kW 20 min 1684x494x762 mm 600 kg
External battery cabinets
1022561 9X55-BAT5-64x7Ah 2x32x7 Ah Check technical specifications 817x305x699 mm 195 kg
1022562 9X55-BAT5-96x7Ah 3x32x7 Ah Check technical specifications 1214x305x699 mm 310 kg
1025169 9355-BAT-1x24Ah (30 kVA) 1x36x24 Ah 1684x494x758 mm 510 kg
1025170 9355-BAT-2x24Ah (30 kVA) 2x36x24 Ah 1684x494x758 mm 870 kg