 Stand-alone UPS with 3-phase input
 External battery cabinets
UPS output power rating (0,9 p.f.)
kVA 8 10 12 15 20 30 40
kW 7,2 9 10,8 13,5 18 27 36
General
Efficiency in double conversion mode (full load) 92% 93%
Efficiency in double conversion mode (half load) 90% 91%
Efficiency in high efficiency mode up to 98% -
Distributed paralleling with Hot Sync technology 4
Field upgradeable yes
Inverter/rectifier topology transformer-free IGBT with PWM
Audible noise < 50 dB
Altitude (max) 1000 m without derating (max 2000 m)
Input
Input wiring 1 ph or 3 ph + N + PE 3 ph + N + PE
Nominal voltage rating (configurable) 220/380, 230/400, 240/415 V 50/60 Hz
Input voltage range Low -20% at 100% load/-50% at 50% load without battery discharge; High +10%/max +20%
Input frequency range 45-65 Hz
Input power factor 0,99
Input ITHD less than 4,5%
Soft start capability Yes
Internal backfeed protection Yes
Output
Output wiring 1 ph or 3 ph + N + PE
Nominal voltage rating (configurable) 220/380, 230/400, 240/415 V 50/60 Hz
Output UTHD <3% (100% linear load); <5% (reference non linear load)
Output power factor 0,9 (e.g. 9 kW at 10 kVA) 0,9 (e.g. 27 kW at 30 kVA)
Permitted load power factor 0,7 lagging - 0,8 leading
Overload on inverter 10 min 100-110%; 1 min 110-125%; 5 sec 125-150%; 300 ms >150%
Overload when bypass available 60 min 100-110%, 10 min 110-125%; 1 min >125- 150%
Battery
Type Maintenance-free VRLA batteries, NiCd
Charging method ABM technology or Float
Temperature compensation Optional
Battery nominal voltage (lead-acid) 384 V (32x12 V, 192 cells) 432 V (36x12 V, 216 cells)
Charging current / Model Default 3 A
*Max 30 A
Default 3 A
*Max 60 A
*May be limited by maximum UPS input current rating
Accessories
  Isolation transformer, long-life batteries, external battery cabinets, UPS Center (input, bypass, distribution), X-Slot connectivity (Web/SNMP, ModBus/ Jbus, Relay, Hot Sync, ViewUPS-X remote display), Hot Sync parallel tie cabinet, integrated manual bypass, external maintenance bypass switch Isolation transformer, long-life batteries, external battery cabinets, X-Slot connectivity (Web/SNMP, ModBus/ Jbus, Relay, Hot Sync, ViewUPS-X remote display), Hot Sync parallel tie cabinet, integrated manual bypass, external maintenance bypass switch
Communications
X-Slot 2 communication bays
Serial ports 1 available
Relay inputs/outputs 2/1 programmable
Compliance with standards
Safety (CB certified) IEC 62040-1, IEC 60950-1
EMC IEC 62040-2
Performance IEC 62040-3

In the interests of continuous product improvement all specifications are subject to change without notice.

Stand-alone UPS with 3-phase input
Part number Description Rating Back-up (p.f. 0.7) Dimensions (HxWxD) Weight
1023411 9355-8-N-15-32x9Ah 8 kVA / 7.2 kW 15 min 817x305x702 mm 160 kg
1023412 9355-8-N-33-64x9Ah 8 kVA / 7.2 kW 33 min 1214x305x702 mm 275 kg
1023413 9355-10-N-10-32x9Ah 10 kVA / 9 kW 10 min 817x305x702 mm 160 kg
1023414 9355-10-N-25-64x9Ah 10 kVA / 9 kW 25 min 1214x305x702 mm 275 kg
1023415 9355-12-N-8-32x9Ah 12 kVA / 10.8 kW 8 min 817x305x702 mm 160 kg
1023416 9355-12-N-20-64x9Ah 12 kVA / 10.8 kW 20 min 1214x305x702 mm 275 kg
1023417 9355-15-N-5-32x9Ah 15 kVA / 13.5 kW 5 min 817x305x702 mm 160 kg
1023418 9355-15-N-15-64x9Ah 15 kVA / 13.5 kW 15 min 1214x305x702 mm 275 kg
1025061 9355-20-N-5-1x9Ah-MBS 20 kVA / 18 kW 5 min 1684x494x762 mm 300 kg
1025062 9355-20-N-13-2x9Ah-MBS 20 kVA / 18 kW 13 min 1684x494x762 mm 400 kg
1025063 9355-20-N-22-3x9Ah-MBS 20 kVA / 18 kW 22 min 1684x494x762 mm 500 kg
1025064 9355-20-N-31-4x9Ah-MBS 20 kVA / 18 kW 31 min 1684x494x762 mm 600 kg
1025065 9355-30-N-7-2x9Ah-MBS 30 kVA / 27 kW 7 min 1684x494x762 mm 400 kg
1025066 9355-30-N-13-3x9Ah-MBS 30 kVA / 27 kW 12 min 1684x494x762 mm 500 kg
1025067 9355-30-N-20-4x9Ah-MBS 30 kVA / 27 kW 20 min 1684x494x762 mm 600 kg
1025795 9355-40-N-8-3x9Ah-MBS 40 kVA / 36 kW 8 min 1684x494x762 mm 517 kg
1025796 9355-40-N-12-4x9Ah-MBS 40 kVA / 36 kW 12 min 1684x494x762 mm 617 kg
External battery cabinets
1022561 9X55-BAT5-64x7Ah 2x32x7 Ah Check technical specifications 817x305x699 mm 195 kg
1022562 9X55-BAT5-96x7Ah 3x32x7 Ah Check technical specifications 1214x305x699 mm 310 kg
1025169 9355-BAT-1x24Ah (30 kVA) 1x36x24 Ah 1684x494x758 mm 510 kg