Eaton Power-Sure 700

The Power-Sure 700 combines voltage regulation with a transformer and filter to remove transients and noise. The combined effect is regulating and shielded isolation transformer/system that solves 99 percent of the electrical disturbance problems, including electrical brownouts, sags, surges, transients and other electrical disturbances.

Eaton Power-Sure 700 – Technical Specifications

Electrical characteristics
Technology Tap changer
Input voltage range +10% to -20%
Output voltage range ±3% typical
Input frequency range 47-53 Hz for 50 Hz models
57-73 Hz for 60 Hz models
Efficiency 97% typical, 95% minimum
Load power factor 0.6 leading to 0.6 lagging
Common-mode noise attenuation 140 dB
Normal-mode noise attenuation -3 dB @ 1000 Hz, -40 dBA per decade
Total harmonic distortion Less than 1% added
Correction time 1 cycle typical, 1.5 cycle maximum
Overload rating 200% for 10 seconds, 1000% for 1 cycle
Overvoltage protection Automatic electronic shutdown if output voltage exceeds +10% for 6 seconds (adjustable)
Environments
Indicator lights Three green lights indicate regulated voltage on each phase. A fourth red light indicates an overtemperature condition
Audible noise Less than 50 dBA @ 1 meter (depending on size)
Operating temperature -10°C to +40°C
Altitude Up to 10,000 ft
Standards
Safety agency UL 1012, CSA, FCC Cat. A
Surge suppression Meets ANSI/IEEE Standard C62.41-1991
Warranty One Year

*Due to continuing product improvement programs, specifications are subject to change without notice

Eaton Power-Sure 700 Model Selection Guide

Part Number kVA Rating By-Pass Metering Cabinet size
H x W x D in
BTUs/hr Weight (lb)
T_ _ -010k- _ 10 Yes No 30.2 x 22.2 x 29.0 1,025 440
T_ _ -010k- _ 10 Yes Yes 44.2 x 22.2 x 29.0 1,205 520
T_ _ -015k- _ 15 Yes No 30.2 x 22.2 x 29.0 1,540 465
T_ _ -015k- _ 15 Yes Yes 44.2 x 22.2 x 29.0 1,540 700
T_ _ -025k- _ 25 Yes No 44.2 x 22.2 x 29.0 2,560 700
T_ _ -030k- _ 30 Yes Yes 44.2 x 22.2 x 29.0 3,090 720
T_ _ -045k- _ 45 Yes Yes 44.3 x 45.9 x 29.0 4,600 950
T_ _ -050k- _ 50 Yes Yes 66.0 x 29.0 x 35.5 7,332 1176
T_ _ -075k- _ 75 Yes Yes 76.0 x 34.4 x 35.5 9,514 1575
T_ _ -100k- _ 100 Yes Yes 76.0 x 34.4 x 35.5 11,833 2014
T_ _ -125k- _ 125 Yes Yes 76.0 x 34.4 x 35.5 14,748 2137
T_ _ -150k- _ 150 Yes Yes 76.0 x 34.4 x 35.5 17,698 2240
T_ _ -225k- _ 225 Yes Yes 77.4 x 56.0 x 41.5 23,000 3300
T_ _ -300k- _ 300 Yes Yes 77.4 x 56.0 x 41.5 30,750 4000
T_ _ -500k- _ 500 Yes Yes 77.0 x 72.4 x 48.4 51,250 5500

* The number listed is not the part number for ordering. You need to utilize the product assist guide for building a part number and ordering.

NOTES:

  • 75-300 kVA are available with 480/600V input only; requires an additional auto-transformer for lower input voltage
  • Listings – UL listed, CSA Certified, except for 600V: no UL, CSA on 600V units
  • For output distribution, call factory
  • K factor rated units available on request

Eaton Power-Sure 700 – Features

  • Processor controlled voltage regulation
  • Tight output voltage regulation
  • Zero-current switching
  • Wide input regulation range
  • Triple shielded, computer grade transformer
  • Highly efficient – 97 percent typical
  • High inrush capability
  • Transient protection and high frequency filter
  • Over/under voltage protection (optional)
  • Includes input circuit breaker
  • Manual bypass switch (optional)

Eaton Power-Sure 700 – Documentation

Eaton Power-Sure 700 – Support

Phone 1-800-809-2772 opt 4,2
Email spd@eaton.com