Eaton Power-Sure 800

The Power-Sure 800 power conditioners provide high quality power with inherent surge protection, noise and bi-directional harmonic filtering, as well as superior isolation. Ideal for industrial, commercial and medical equipment.

Eaton Power-Sure 800 – Technical Specifications

Electrical characteristics
Line regulation ±2% V-out for +10% to -20% V-in at 100% load
Load regulation ±3% for 0% to 75% load, ±2% for 100% load
Immunity to distortion @ 40% THD V-in, 5% Max TCH V-out
Ride-through capability 1 cycle
Voltage recovery 2 cycles to 95%, 3 cycles to 100%
K-factor K-30 rated
Power factor correction Input of 0.95 typical
Harmonic attenuation -23 dB for load reflected harmonics
Galvanic isolation NEC 25-5d, 0.001 PF
Surge protection UL 1449 Rating 330V; ANSI/IEEE 62.41-Cat B3
Common mode noise attenuation 140 dB
Transverse mode noise attenuation 120 dB
Reliability 200,000 hours (MTBF)
Audible noise 52 dB to 56 dB measured at 1 meter, A scale
Efficiency Approximately 92% at full load
Operating temperature -20ºC to +40ºC
Safety UL 1012, UL 544, cUL
Warranty Two-year warranty

*Due to continuing product improvement programs, specifications are subject to change without notice


Eaton Power-Sure 800 Model Selection Guide

Part Number Rating (VA/Watts) Input voltage Output voltage Input interface Output interface Dimensions
(H x W x D, in)
Weight (lb)
Office models with receptacles
T800R-00500 500/400 120 120 5-15P (4) 5-20R 8.50 x 12.75 x 9.50 32
T800R-00700 700/500 120 120 5-15P (4) 5-20R 8.50 x 12.75 x 9.50 35
T800R-00850 850/600 120 120 5-15P (4) 5-20R 8.50 x 12.75 x 9.50 37
T800R-01000 1000/700 120 120 5-15P (4) 5-20R 8.50 x 12.75 x 17.50 46
T800R-01600 1600/1200 120 120 5-15P (4) 5-20R 8.50 x 12.75 x 17.50 62
T800R-02100 2100/1500 120 120 5-20P (4) 5-20R 8.50 x 12.75 x 17.50 65
T800R-02500 2500/1750 120 120 5-30P (4) 5-20R 8.50 x 12.75 x 17.50 68
T800R-03500 3500/2450 120 120/240 5-50P (4) 5-20R 8.50 x 12.75 x 17.50 72
T800R-03501 3500/2450 208/240 120/240 6-20P (4) 5-20R 8.50 x 12.75 x 17.50 73
T800R-05000 5000/3500 208/240 120/240 Hardwired Custom* 15.00 x 23.75 x 22.50 176
T800R-07500 7500/5250 208/240 120/240 Hardwired Custom* 15.00 x 23.75 x 22.50 210
T800R-10000 10000/7000 208/240 120/240 Hardwired Custom* 15.00 x 23.75 x 22.50 256
T800R-15000 15000/10500 208/240 120/240 Hardwired Custom* 15.00 x 23.75 x 22.50 314
Industrial models (hardwired wall-/panel-mount)
T800P-00500 500/500 Range 1 Range 3 Hardwired Hardwired 9.00 x 14.00 x 10.00 52
T800P-00750 750/750 Range 1 Range 3 Hardwired Hardwired 9.00 x 14.00 x 10.00 60
T800P-01000 1000/1000 Range 1 Range 3 Hardwired Hardwired 9.00 x 14.00 x 10.00 82
T800P-01500 1500/1500 Range 1 Range 3 Hardwired Hardwired 13.00 x 16.50 x 14.75 106
T800P-02000 2000/2000 Range 1 Range 3 Hardwired Hardwired 13.00 x 16.50 x 14.75 125
T800P-03500 3000/3000 Range 1 Range 3 Hardwired Hardwired 13.00 x 16.50 x 14.75 157
T800P-05000 5000/5000 Range 1 Range 3 Hardwired Hardwired 27.00 x 22.50 x 28.50 437
T800P-08000 8000/8000 Range 2 Range 3 Hardwired Hardwired 27.00 x 22.50 x 28.50 495
T800P-10000 10000/10000 Range 2 Range 3 Hardwired Hardwired 27.00 x 22.50 x 28.50 537
Industrial models (hardwired floor-mount)
T800F-05000 5000/5000 Range 1 Range 3 Hardwired Hardwired 23.00 x 20.00 x 28.50 407
T800F-08000 8000/8000 Range 2 Range 3 Hardwired Hardwired 23.00 x 20.00 x 28.50 465
T800F-10000 10000/10000 Range 2 Range 3 Hardwired Hardwired 23.00 x 20.00 x 28.50 507
T800F-15000 15000/15000 Range 2 Range 3 Hardwired Hardwired 35.00 x 25.00 x 39.50 830
T800F-20000 20000/20000 Range 2 Range 3 Hardwired Hardwired 35.00 x 25.00 x 39.50 950
T800F-25000 25000/25000 Range 2 Range 3 Hardwired Hardwired 35.00 x 25.00 x 39.50 1070

*See custom output receptacles chart below

I/O Range Voltage Range
Range 1: 120/208/240/480
Range 2: 208/240/480
Range 3: 120/208/240


Eaton Power-Sure 800 Custom Output Receptacles – 5-15 KVA Office Models Only

Suffix NEMA receptacles Volts Amps Output panel used
A (1) 5-15R 120 15 1
B (2) 5-15R 120 15 1
C (1) 5-20R 120 20 1
D (2) 5-20R 120 20 1
E (1) 5-30R 120 30 1.5
F (1) 6-15R 208/240 15 1
G (2) 6-15R 208/240 15 1
H (1) 6-20R 208/240 20 1
I (2) 6-20R 208/240 20 1
J (1) 6-30R 208/240 30 1.5
K (1) 6-50R 208/240 50 1.5
L (1) 14-20R 120/240 20 1
M (1) 14-30R 120/240 30 1.5
N (1) L5-15R 120 15 1
P (2) L5-15R 120 15 1
R (1) L5-20R 120 20 1
S (1) L5-30R 120 30 1
T (1) L6-15R 208/240 15 1
U (2) L6-15R 208/240 15 1
V (1) L6-20R 208/240 20 1
W (1) L6-30R 208/240 30 1
X (1) L14-20R 120/240 20 1
Y (1) L14-30R 120/240 30 1

Note: For isolated ground receptacles, add IG to part numbers

Eaton Power-Sure 800 – Features

  • Superior isolation
  • Tight output voltage regulation
  • High immunity to distortion
  • Lightning and surge protection
  • Protection against power interruptions
  • Power factor correction
  • Bi-directional harmonic filtering
  • Meets ANSI standards for computers with inputs as low as 50 percent of nominal
  • UL 1012, UL 544 and cUL Listed
  • K-30 rated design

Eaton Power-Sure 800 – Documentation

Power-Sure 800 - Product Assist
English (US)
7-Oct-2015
109 kB
Power conditioning products
English
12-Aug-2014
1392 kB
Power-Sure 800 - User Manual
English (US)
15-Sep-2015
1435 kB
Power-Sure 800 Technical Data
English (US)
15-Sep-2015
1185 kB

Eaton Power-Sure 800 – Support

Phone 1-800-809-2772 opt 4,2
Email spd@eaton.com